3.1601.3 Support

Topic: 
Ducts
Subtopic: 
Duct Preparation
Desired Outcome: 
Ducts and plenums properly supported
TitleSpecification(s)Objective(s)
3.1601.3a
Support (applies to all duct types)

Flexible and duct board ducts and plenums will be supported every 4' using a minimum of 1 ½" wide material

Support materials will be applied in a way that does not crimp ductwork or cause the interior dimensions of the ductwork to be less than specified (e.g., ceiling, framing, strapping); duct support must be installed in accordance with authority having jurisdiction

Metal ducts will be supported by 1/2 inch wide eighteen gauge metal straps or 12-gauge galvanized wire at intervals not exceeding 10 feet or other approved means

Eliminate falling and sagging