3.1602.20 Proprietary Spray Application

Topic: 
Ducts
Subtopic: 
Duct Sealing
Desired Outcome: 
Ducts and plenums are sealed to prevent leakage
For supporting material, see Referenced Standards.
TitleSpecification(s)Objective(s)
3.1602.20a
Internal or external application

Installation of sealant will be applied in a way that meets manufacturer specifications, as well as UL UL Underwriters Laboratories 181M, NFPA NFPA National Fire Protection Association, www.nfpa.org 90A, and NFPA NFPA National Fire Protection Association, www.nfpa.org 90B

Reduce duct leakage

3.1602.20b
Installation

If specified, internally applied spray or aerosol sealing will only be applied after any manual sealing of large gaps is complete

Installer will coordinate access to the ductwork in the affected dwelling units with the building/property management and specialized subcontractor(s)

Installer will provide logistical support to subcontractor(s) (e.g., mask duct terminations and openings, manually seal ducts, install flow orifices)

Sealants and sprays will be applied according to manufacturer specifications by a qualified contractor

Eliminate air leakage into or out of ducts and plenums

Ensure occupant and worker safety

Provide proper sequence of duct improvements

Minimize inconvenience to occupants