Safe and effective fan control that supports the ventilation strategy
Specifications
- SF
- MH
- MF
Specification | Objective |
---|---|
Install controls that are either internal to the fan or external For intermittent ventilation strategies: Install a controller that can operate the fan intermittently to produce the intended flow For continuous ventilation strategies: Install an automatic controller that can operate the fan continuously to meet the intended flow rate Only use continuous operation controls on fans containing ECM motors rated for continuous operation |
Meet intended ventilation strategy |
- SF
- MH
- MF
Specification | Objective |
---|---|
Install a manual override control to activate the fan as necessary Occupancy sensors/humidistat: Install an occupancy sensor and/or humidistat designed to function with the chosen fan and in accordance with manufacturer specifications Carbon dioxide sensors (demand control): Only use CO2 sensors with VFD or multispeed fans |
Provide ventilation on an as-needed basis |
- SF
- MH
- MF
Specification | Objective |
---|---|
Install a clearly labeled manual service disconnect for all ventilation fan controls |
Service disconnect available |
- SF
- MH
- MF
Specification | Objective |
---|---|
Clearly label all whole-house ventilation system controls "Whole-House Ventilation Control" |
Fan control operation made clear |