Safe and reliable water temperature control
Specifications
- SF
- MH
- MF
Specification | Objective |
---|---|
Verify current plumbing infrastructure is sufficient to support the installation(s) and is leak-free |
Verify adequacy of plumbing |
- SF
- MH
- MF
Specification | Objective |
---|---|
Install mixing valves at as many locations as necessary to deliver safe and adequate hot water |
Optimal water temperature throughout the system |
- SF
- MH
- MF
Specification | Objective |
---|---|
Install valve and plumbing to allow for inspection, maintenance, and replacement of the appliance and its components, without disturbing other installed equipment, controls, piping, and components, other than what requires repair/replacement |
Ensure the valve can be readily maintained and replaced |
- SF
- MH
- MF
Specification | Objective |
---|---|
Install a separate water cut-off valve for both the hot and cold incoming water lines |
Allow isolation and service of mixing valve |
- SF
- MH
- MF
Specification | Objective |
---|---|
Install check valves on the hot and cold water supply lines upstream of the mixing valve |
Eliminate crossover |
- SF
- MH
- MF
Specification | Objective |
---|---|
Install mixing valve with a heat trap or at a distance from heat sources sufficient enough to prevent scaling or damage to the valve |
Prevent scaling and valve damage |
- SF
- MH
- MF
Specification | Objective |
---|---|
Install temperature gauges on hot, cold, and tempered supply water lines within sight of the mixing valve |
Verification of proper mixing valve operation |
- SF
- MH
- MF
Specification | Objective |
---|---|
Install controls and sensors in accordance with manufacturer specifications and applicable code (NFPA 70) When controls are low voltage, separate the low voltage and line voltage wiring |
Safe and compliant mixing valve operation |
- SF
- MH
- MF
Specification | Objective |
---|---|
Install dielectric unions when connecting copper to galvanized steel piping in accordance with the IRC and manufacturer specifications |
Prevent corrosion between dissimilar metals |
- SF
- MH
- MF
Specification | Objective |
---|---|
Set discharge temperature to not exceed 120 degrees or as prescribed by local code |
Prevent biological growth in tank but prevent scalding |
- SF
- MH
- MF
Specification | Objective |
---|---|
Provide occupants/owners with user's manual, warranty information, installation instructions, and installer contact information |
Manufacturer supplied information available to occupant |