Version 2020 14/08/2020 - 14:23 4.0104.5e Installation

Apply SPF to prescribed R-value in a continuous layer over entire surface of knee wall from roof deck to attic floor air barrier using a pass thickness maximum in accordance with manufacturer specifications

In colder climates (IECC Zones 5-8), install SPF to a thickness of at least a class II vapor retarder or have at least a class II vapor retarder coating or covering in direct contact with the underside of the SPF

Continuous and contiguous pressure and thermal boundary that prevents vapor intrusion