Version 2020 | 14/08/2020 - 14:25 | 4.0401.1e | Installation | Apply SPF to prescribed R-value in a continuous layer from subfloor surface, over band/rim joist and sill/wall plate, and in contact with foundation or ceiling below using a pass thickness maximum as indicated by manufacturer specifications Install to a thickness of least a class II vapor retarder or have at least a class II vapor retarder coating or covering in direct contact with the interior (or warm) side of the SPF |
Continuous pressure and thermal boundary that prevents moisture vapor movement |
Black Line | ||
Version 2020 | 14/08/2020 - 14:25 | 4.0401.1e | Installation | Apply SPF to prescribed R-value in a continuous layer from subfloor surface, over band/rim joist and sill/wall plate, and in contact with foundation or ceiling below using a pass thickness maximum as indicated by manufacturer specifications Install to a thickness of least a class II vapor retarder or have at least a class II vapor retarder coating or covering in direct contact with the interior (or warm) side of the SPF |