Specification History
SWS Version | Created | Specification ID | Title | Specification | Objective | Supporting Materials | Rationale | Status |
---|---|---|---|---|---|---|---|---|
Version 2020 | 14/08/2020 - 14:25 | 5.0103.1d | Insulation | Insulate all suction lines to a minimum of R-4 with an insulation that is a class II or better vapor retarder Insulate all high pressure lines that pass through spaces where condensation may occur to a minimum of R-4 with an insulation that is a class II or better vapor retarder Seal all seams, joints, etc. of insulation using compatible material (e.g., tape) Install UV-resistant insulation on exterior lines or protected insulation from UV degradation |
Prevent excessive heat gain, condensation and UV degradation |
Black Line | ||
Version 2020 | 14/08/2020 - 14:25 | 5.0103.1d | Insulation | Insulate all suction lines to a minimum of R-4 with an insulation that is a class II or better vapor retarder Insulate all high pressure lines that pass through spaces where condensation may occur to a minimum of R-4 with an insulation that is a class II or better vapor retarder Seal all seams, joints, etc. of insulation using compatible material (e.g., tape) Install UV-resistant insulation on exterior lines or protected insulation from UV degradation |
Prevent excessive heat gain, condensation and UV degradation |
Black Line |