Version 2020 14/08/2020 - 14:26 5.0108.2k Condensate drainage

Pipe condensate to a safe outdoor location where it is drained without contacting the outdoor unit and provide the condensate piping with traps as specified by the manufacturer and applicable building code

When there is potential for freezing of the drain line, insulate condensate drain lines to a minimum of R-4 with insulation that contains a Class II or greater vapor retarder

Drain condensate away from unit and prevent damage