Specification History
SWS Version | Created | Specification ID | Title | Specification | Objective | Supporting Materials | Rationale | Status |
---|---|---|---|---|---|---|---|---|
Version 2020 | 14/08/2020 - 14:26 | 5.0108.3p | Condensate | Install an independent condensate drain for each indoor unit according to SWS for "Condensate Disposal" Install a float switch in the drain pan that interlocks with the cooling system power to turn unit off when pan is not draining Pipe condensate to a properly sized sanitary drain or the outdoors When there is potential for condensation or freezing of the drain line, insulate condensate drain lines to a minimum of R-4 with insulation that contains a Class II or greater vapor retarder |
Independent and functional condensate drainage that prevents water damage |
Black Line | ||
Version 2020 | 14/08/2020 - 14:26 | 5.0108.3p | Condensate | Install an independent condensate drain for each indoor unit according to SWS for "Condensate Disposal" Install a float switch in the drain pan that interlocks with the cooling system power to turn unit off when pan is not draining Pipe condensate to a properly sized sanitary drain or the outdoors When there is potential for condensation or freezing of the drain line, insulate condensate drain lines to a minimum of R-4 with insulation that contains a Class II or greater vapor retarder |
Independent and functional condensate drainage that prevents water damage |
Black Line |