Version 2020 14/08/2020 - 14:26 6.0101.2c Location

Install termination to exhaust to the outdoors, which does not include unconditioned spaces such as attics and crawl spaces that are ventilated with the outdoors

Install terminations:

A minimum of 3' away from any property line;

A minimum of 3' away from operable opening to houses;

A minimum of 10' away from mechanical intake;

Above the snow-line.

If the termination is at the soffit, seal all soffit vents within 6' of the termination

Prevent exhaust from reentering the structure