Specification History

SWS Version Created Specification ID Title Specification Objective Supporting Materials Rationale Status
Version 2020 14/08/2020 - 14:26 6.0101.3c Location

Install intake to pull air from the outdoors, which does not include unconditioned spaces such as attics and crawl spaces that are ventilated with the outdoors

Install intake:

A minimum of 6" from grade;

A minimum of 10' from contaminant sources or exhaust outlets;

Above local snow or flood line;

A minimum of 18" above an asphalt based roof;

Never on a flat roof

Unrestricted entry of contaminant-free air

Black Line
Version 2020 14/08/2020 - 14:26 6.0101.3c Location

Install intake to pull air from the outdoors, which does not include unconditioned spaces such as attics and crawl spaces that are ventilated with the outdoors

Install intake:

A minimum of 6" from grade;

A minimum of 10' from contaminant sources or exhaust outlets;

Above local snow or flood line;

A minimum of 18" above an asphalt based roof;

Never on a flat roof

Unrestricted entry of contaminant-free air

Black Line