Specification History
SWS Version | Created | Specification ID | Title | Specification | Objective | Supporting Materials | Rationale | Status |
---|---|---|---|---|---|---|---|---|
Version 2020 | 14/08/2020 - 14:26 | 6.0101.3c | Location | Install intake to pull air from the outdoors, which does not include unconditioned spaces such as attics and crawl spaces that are ventilated with the outdoors Install intake: A minimum of 6" from grade; A minimum of 10' from contaminant sources or exhaust outlets; Above local snow or flood line; A minimum of 18" above an asphalt based roof; Never on a flat roof |
Unrestricted entry of contaminant-free air |
Black Line | ||
Version 2020 | 14/08/2020 - 14:26 | 6.0101.3c | Location | Install intake to pull air from the outdoors, which does not include unconditioned spaces such as attics and crawl spaces that are ventilated with the outdoors Install intake: A minimum of 6" from grade; A minimum of 10' from contaminant sources or exhaust outlets; Above local snow or flood line; A minimum of 18" above an asphalt based roof; Never on a flat roof |
Unrestricted entry of contaminant-free air |
Black Line |