Version 2020 14/08/2020 - 14:27 6.0304.1a Exterior intake location

Install intake to pull air from the outdoors, which does not include unconditioned spaces such as attics and crawl spaces that are ventilated with the outdoors

Install intake:

A minimum of 6" from grade;

A minimum of 10' from contaminant sources or exhaust outlets;

Above local snow or flood line;

A minimum of 18" above an asphalt based roof;

Never on a flat roof

Unrestricted entry of contaminant-free air