Specification History
SWS Version | Created | Specification ID | Title | Specification | Objective | Supporting Materials | Rationale | Status |
---|---|---|---|---|---|---|---|---|
Version 2025 | 24/09/2023 - 17:11 | 7.0302.1f | TandP valve and piping | Install a Temperature and Pressure (TandP) relief valve per the IRC and manufacturer specifications Pipe the valve 6" or less from the floor or drain pan or to the outdoors and must terminate in an observable location Select piping material based on IRC requirements |
Direct scalding water away from occupants |
Language was changed to align with 2.0103.1c for consistency. The pipe should be installed from the T&P valve to no greater than 6 inches off the floor. It cannot be more than 6" from the floor per the IRC, nor should it be for occupant safety. | Red Line | |
Version 2020 | 14/08/2020 - 14:28 | 7.0302.1f | TandP valve and piping | Install a Temperature and Pressure (TandP) relief valve per the IRC and manufacturer specifications Pipe the valve to within 6" of the floor or drain pan or to the outdoors and must terminate in an observable location Select piping material based on IRC requirements |
Direct scalding water away from occupants |
Black Line | ||
Version 2020 | 14/08/2020 - 14:28 | 7.0302.1f | TandP valve and piping | Install a Temperature and Pressure (TandP) relief valve per the IRC and manufacturer specifications Pipe the valve to within 6" of the floor or drain pan or to the outdoors and must terminate in an observable location Select piping material based on IRC requirements |
Direct scalding water away from occupants |
Black Line |