Version 2020 14/08/2020 - 14:25 5.0104.1d Termination design

Design terminations using ANSI/ACCA Manual T (Air Distribution Basics)

Terminations must be capable of delivering air with proper speed and throw of 80-120% of the farthest wall, floor, or ceiling they serve, and must have a noise level less than 30 decibels

Return grille gross area will be equal to or larger than return box

Appropriate level of air mixing, air flow, and occupant comfort

Black Line