Continuous, weathertight air and thermal boundary that maintains door operability
Specifications
- SF
- MH
- MF
Specification | Objective |
---|---|
Select sealants that: are compatible with their intended surfaces, allow for differential expansion and contraction between dissimilar materials, meet the requirements of the applicable fire safety code (e.g., thermal or ignition barriers), and for use inside the pressure boundary select low volatile organic compound (VOC) sealants that meet independent testing and verification protocols |
Select safe and effective sealants |
- SF
- MH
- MF
Specification | Objective |
---|---|
Select: pest-resistant materials that adequately support applied load and are permanent air barriers, materials that meet the requirements of the applicable fire safety code (e.g., thermal or ignition barriers), and low volatile organic compound (VOC) materials for use inside the pressure boundary that meet independent testing and verification protocols |
Select safe and effective materials |
- SF
- MH
- MF
Specification | Objective |
---|---|
Select doors that meet the SHGC, U-value, and air leakage requirements of the work order Select doors that meet the egress and safety glass requirements of the location where they are installed |
Choose correct and safe new door |
- SF
- MH
- MF
Specification | Objective |
---|---|
Remove existing door frame and all components Replace any damaged or rotting framing Remove any material from the sealing area that will prevent full adhesion of the selected sealant Remove any material from the installation area that will prevent a level and firm installation Seal the rough opening to the wall system's air and thermal boundary with non-expanding sealants Install flashing to direct water away from the door opening in accordance with manufacturer's instructions |
Rough opening sealed, insulated, and properly prepared for installation |
- SF
- MH
- MF
Specification | Objective |
---|---|
Install new door in accordance with manufacturer specifications in alignment with the wall system's air and thermal boundary Install exterior flashing and weatherstripping per the manufacturer's specifications Gaps between the new door frame and the rough opening will be sealed with low-expanding foam Door rail (bottom) and threshold will be adjusted to ensure tight but operable fit Final installation will be air and watertight |
Continuous and contiguous air and thermal boundary |
- SF
- MH
- MF
Specification | Objective |
---|---|
Verify safe operation of door and all components Where doors are required to have a fire-resistance rating, all weather strips and sealants applied to the door will be compatible with the listing of the door |
Safe egress and fire safety maintained |