Continuous, contiguous, safe, and compliant thermal boundary that prevents air movement @ 50 Pascals
Specifications
- SF
- MF
Specification | Objective |
---|---|
Verify that installation area is free of: active water leaks, fuel leaks (i.e., gas, oil, propane), and pest intrusions energized knob and tube wiring uncovered electrical junctions improperly terminated devices (ventilation fans, dryers, plumbing stacks, condensate lines, combustion appliance flues/chimneys, etc.) high-temperature devices (non-IC rated recessed lights, chimneys, flues, vents, etc.) unless they are zero clearance devices insulation escape openings Verify that installation area is: intact and able to support insulation weight and installation pressure |
Ensure space can be safely insulated |
- SF
- MF
Specification | Objective |
---|---|
Install airtight, rigid, blocking material at all cavity openings that aligns with the pressure boundary and will not fail under dense pack pressures |
Durable and airtight insulation cavity that aligns with the pressure boundary |
- SF
- MF
Specification | Objective |
---|---|
Fill 100% of each cavity with insulation to the correct density that prevents air movement |
Complete, consistent, and airtight insulation coverage |
- SF
- MF
Specification | Objective |
---|---|
Install closure system over all access holes that is airtight, and permanent |
Airtight, durable access closure |
- SF
- MF
Specification | Objective |
---|---|
Post a dated receipt signed by the installer that minimally includes: Installed insulation type, coverage area, installed thickness, minimum settled thickness, installed R-value, and number of bags installed |
Comply with 16 CFR 460.17 and document contract compliance |