Continuous, contiguous, safe, and compliant thermal boundary that prevents air movement @ 50 Pascals
Specifications
- SF
- MH
- MF
Specification | Objective |
---|---|
Verify that installation area is free of: active water leaks, fuel leaks (i.e., gas, oil, propane), and pest intrusions energized knob and tube wiring uncovered electrical junctions improperly terminated devices (ventilation fans, dryers, plumbing stacks, condensate lines, combustion appliance flues/chimneys, etc.) high-temperature devices (non-IC rated recessed lights, chimneys, flues, vents, etc.) unless they are zero clearance devices insulation escape openings Verify that installation area is: intact, able to support insulation weight and pressure, and air sealed (including blockers under kneewalls in alignment with the interior side of the kneewall) |
Ensure space can be safely insulated |
- SF
- MH
- MF
Specification | Objective |
---|---|
Install airtight, rigid, blocking material at all cavity openings that aligns with the pressure boundary and will not fail under dense pack pressures |
Durable and airtight insulation cavity that aligns with the pressure boundary |
- SF
- MH
- MF
Specification | Objective |
---|---|
Install airtight backing material over entire area to be insulated that will withstand dense packing pressures Secure backing material using mechanical fasteners that penetrate the sub framing a minimum of 1" Installation must have a minimum of a 30-year service life |
Airtight, durable insulation backing |
- SF
- MH
- MF
Specification | Objective |
---|---|
Fill 100% of each cavity with insulation to the correct density that prevents air movement |
Complete, consistent, and airtight insulation coverage |
- SF
- MH
- MF
Specification | Objective |
---|---|
Install closure system over all access holes that is airtight and permanent |
Airtight, durable, access closure |
- SF
- MH
- MF
Specification | Objective |
---|---|
Separate all foam products from living space with a thermal barrier material (e.g., 1/2" gypsum wallboard) as specified by applicable building code If attic is used only for the service of utilities, foam will be separated from the attic space using a suitable ignition barrier covering or coating according to manufacturer's specifications If attic is used for storage or occupancy, spray foam will be separated from the attic space using a thermal barrier material (e.g., 1/2" gypsum wallboard) as specified by applicable building code and manufacturer specifications If code requirements are unclear, consult local code officials for clarification |
Minimize ignition and combustion potential |
- SF
- MH
- MF
Specification | Objective |
---|---|
Post a dated receipt signed by the installer that minimally includes: Installed insulation type, coverage area, installed thickness, minimum settled thickness, installed R-value, and number of bags installed |
Comply with 16 CFR 460.17 and document contract compliance |