Continuous, contiguous, and safe thermal boundary that prevents air movement @ 50 Pascals
Specifications
- SF
- MF
Specification | Objective |
---|---|
Verify that installation area is free of: active water leaks, fuel leaks (i.e., gas, oil, propane), and pest intrusions energized or undammed knob and tube wiring uncovered electrical junctions improperly terminated devices (ventilation fans, dryers, plumbing stacks, condensate lines, combustion appliance flues/chimneys, etc.) unshielded high-temperature devices (non-IC rated recessed lights, chimneys, flues, vents, etc.) unless they are zero clearance devices insulation escape openings Verify that installation area is: intact, able to support insulation weight, and air sealed Verify all plumbing and ductwork will be inside the thermal boundary |
Ensure space can be safely insulated |
- SF
- MF
Specification | Objective |
---|---|
Prepare the surface according to manufacturers specifications Install durable backing material over any escape holes in the air barrier and utility junctions that will be covered with SPF Install flags that can be seen below the floor joists at all utility junctions for future identification and ensure utility junctions remain accessible per local code requirements |
Prevent SPF leakage, identify utility junctions for future |
- SF
- MF
Specification | Objective |
---|---|
Apply SPF to prescribed R-value to bottom side of floor deck and top of support beams using a pass thickness maximum as indicated by manufacturer specifications Install to a thickness of least a class I vapor retarder or have at least a class I vapor retarder coating or covering in direct contact with the underside of the SPF |
Continuous pressure and thermal boundary that prevents moisture vapor movement |
- SF
- MF
Specification | Objective |
---|---|
Separate all foam products from living space with a thermal barrier material (e.g., 1/2" gypsum wallboard) as specified by applicable building code If space is used only for the service of utilities, foam will be separated from the space using a suitable ignition barrier covering or coating according to manufacturer's specifications If space is used for storage or occupancy, spray foam will be separated from the space using a thermal barrier material (e.g., 1/2" gypsum wallboard) as specified by applicable building code and manufacturer specifications If code requirements are unclear, consult local code officials for clarification |
Minimize ignition and combustion potential |
- SF
- MF
Specification | Objective |
---|---|
Post a dated receipt signed by the installer that minimally includes: Installed insulation type, coverage area, installed thickness, and installed R-value |
Comply with 16 CFR 460.17 and document contract compliance |