Continuous, contiguous, safe, pest and weather resistant thermal boundary that prevents air movement @ 50 Pascals
Specifications
- SF
- MH
- MF
Specification | Objective |
---|---|
Verify that installation area is free of: active water leaks, fuel leaks (i.e., gas, oil, propane), and pest intrusions energized knob and tube wiring uncovered electrical junctions improperly terminated devices (ventilation fans, dryers, plumbing stacks, condensate lines, combustion appliance flues/chimneys, etc.) high-temperature devices (non-IC rated recessed lights, chimneys, flues, vents, etc.) unless they are zero clearance devices insulation escape openings Verify that installation area is: intact and able to support insulation weight and pressure |
Ensure space can be safely insulated |
- SF
- MH
- MF
Specification | Objective |
---|---|
Select insulation that has a flame spread and smoke development index of 25/450 or less and backing material that has a smoke development index of 450 or less when tested in accordance with ASTM E84 or UL 723 Select rigid backing material that: is a permanent air barrier will support installed insulation without failure |
Select fire safe materials |
- SF
- MH
- MF
Specification | Objective |
---|---|
Select sealants that: are compatible with their intended surfaces allow for differential expansion and contraction between dissimilar materials meet the requirements of the applicable fire safety code (e.g., thermal or ignition barriers) |
Select safe and effective sealants |
- SF
- MH
- MF
Specification | Objective |
---|---|
Install airtight, rigid, blocking material at all cavity openings that aligns with the pressure boundary and will not fail under dense pack pressures |
Prevent insulation gaps or voids |
- SF
- MH
- MF
Specification | Objective |
---|---|
Mechanically fasten a continuous rigid barrier to underside of floor assembly that is suitable to withstand weather, moisture, and pest contact, and with a fire-resistance rating equal to the resistance rating of the original floor assembly |
Insulation protected from weather, pests, and moisture |
- SF
- MH
- MF
Specification | Objective |
---|---|
Fill 100% of each cavity to manufacturer's density requirements keeping insulation in full contact with the air barrier |
Complete, consistent, and airtight insulation coverage |
- SF
- MH
- MF
Specification | Objective |
---|---|
Install closure system over all access holes that is airtight and permanent |
Airtight, durable, access closure |
- SF
- MH
- MF
Specification | Objective |
---|---|
Seal all seams, joints, connections, penetrations, etc. in the rigid protective barrier with compatible sealant Stuff any gaps larger than 1/4" with copper metal mesh or steel wool prior to sealing Cover exposed corners of the rigid protective barrier with reinforced hardware cloth or metal board bead |
Airtight, pest resistant exterior |
- SF
- MH
- MF
Specification | Objective |
---|---|
Apply a weather-resistant barrier to the exposed side of the insulation (e.g., exterior insulated finishing system and spray-on roof waterproofing over foam) |
Protect insulation from weather, light and impact |
- SF
- MH
- MF
Specification | Objective |
---|---|
Post a dated receipt signed by the installer that minimally includes: Installed insulation type, coverage area, installed thickness, minimum settled thickness, installed R-value, and number of bags installed |
Comply with 16 CFR 460.17 and document contract compliance |