Effective, efficient, safe, and durable return air system
Specifications
- MH
Specification | Objective |
---|---|
Close and seal existing return air openings in accordance with SWS detail for "Duct Repair: Mechanical Fastening" and SWS Subtopic "Duct Sealing" |
Reduce air leakage and improve indoor air quality |
- MH
Specification | Objective |
---|---|
Provide alternate return air opening to the furnace closet (e.g., louvered door or install grilles) Net free air flow must minimally meet manufacturer specifications for the installed equipment |
Ensure sufficient return air is provided to the system |
- MH
Specification | Objective |
---|---|
Seal entire return cavity with durable materials and UL 181 approved mastic and mesh tape (i.e., no foam allowed inside return systems) |
Minimize return leakage |
- MH
Specification | Objective |
---|---|
Provide accessible filter grill and filter with no air bypass of the filter |
Provide return air filtration without air bypass |