Safe, compliant, and effective system installation in which sequence of operation is correct
Specifications
- SF
- MF
Specification | Objective |
---|---|
Perform residential load calculation in accordance with the current version of ANSI/ACCA Manual J (Residential Load Calculation) or equivalent using interior design temperatures of 70 degrees for heating Perform commercial load calculation in accordance with the current version of ANSI/ACCA Manual N (Commercial Load Calculation) or equivalent using interior design temperatures of 70 degrees for heating Room by room load calculations will be performed when installing new distribution system components or in retro-commissioning projects Calculated loads based on post-retrofit dwelling characteristics including distribution system |
Equipment design load calculated correctly for post-retrofit dwelling |
- SF
- MF
Specification | Objective |
---|---|
Select residential equipment in accordance with the current version of ANSI/ACCA Manual S (Residential Equipment Selection) or equivalent Select commercial equipment in accordance with the current version of ANSI/ACCA Manual CS (Commercial Applications, Systems and Equipment) or equivalent Select heating equipment of the lowest capacity required to meet the design heating load and provide sufficient volume for components of existing distribution system that will not be replaced Select system that is ENERGY STAR® certified or equivalent |
Select efficient equipment capable of meeting the design load |
- SF
- MF
Specification | Objective |
---|---|
Install unit in a dry location and within conditioned space (when feasible) Install equipment in a location and manner to provide ease of access for routine maintenance/service |
Safe, accessible, and corrosion-resistant location |
- SF
- MF
Specification | Objective |
---|---|
Situate equipment on a stable, non-wicking, and fireproof material Ensure unit is level, stable and supported independently of the distribution system |
Safe, stable, and durable equipment installation |
- SF
- MF
Specification | Objective |
---|---|
Install electrical wiring according to NFPA 70, and Provide an electrical disconnect within site of the unit Install all high voltage wiring inside of protective conduit and approved junction boxes, no wiring connections (high or low voltage) will occur outside of appropriate junction box |
Safe and compliant electrical wiring installation |
- SF
- MF
Specification | Objective |
---|---|
Install equipment connections (e.g., electrical service, drains, fuel, venting) to allow for necessary service and repair access to all portions of the equipment |
Connections do not interfere with operation and service of equipment |
- SF
- MF
Specification | Objective |
---|---|
Provide occupants/owners with user's manual, warranty information, installation instructions, and installer contact information |
Provide occupants and service technicians with instructions |