Safe, leak free, and optimal gas supply to all gas-fired equipment
Specifications
- SF
- MH
- MF
Specification | Objective |
---|---|
Locate/route gas piping/train so as to not create a trip hazard, not be damaged by water, and to create the least pressure drop possible |
Durable, safe, and effective installation |
- SF
- MH
- MF
Specification | Objective |
---|---|
All piping installations must contain at a minimum a manual gas shut off valve, union joint, and a sediment trap at each appliance |
Safely allow service, replacement, and emergency shutoff of individual appliances Protect appliance from moisture and debris in gas |
- SF
- MH
- MF
Specification | Objective |
---|---|
If installed, vent all gas pressure regulators requiring venting to outside the building with code approved rigid pipe Terminate pipe in a safe location without any thread, coupling, fitting, etc. that would allow a plug to be easily fitted |
Vent flammable gasses outside the building |
- SF
- MH
- MF
Specification | Objective |
---|---|
Seal all gas piping in accordance with manufacturer specifications |
Leak free gas piping |
- SF
- MH
- MF
Specification | Objective |
---|---|
Install a secondary LP safety detector system (e.g., valve, exhaust fan, alarm light) for propane piping installed below grade |
Detect accumulation of dangerous levels of propane in areas that are below grade |
- SF
- MH
- MF
Specification | Objective |
---|---|
If a gas pressure booster is necessary, confirm compatibility with the gas-fired equipment and check low and high gas pressure switches for proper operation |
Gas pressure booster is compatible and safe |