Provide adequate fresh air and maintain desired indoor humidity
Specifications
- SF
- MF
Specification | Objective |
---|---|
Equipment must be ENERGY STAR® rated and must have an auto-restart to maintain settings through power failures Dehumidification ventilator will be a ducted unit and will provide outside air to the home or space |
Ensure efficient dehumidification and fresh air |
- SF
- MF
Specification | Objective |
---|---|
Size the system with enough capacity to handle humidity from outside air ventilation and internal gains Maintain humidity levels inside the home at less than 60% relative humidity For residential applications, follow ASHRAE 62.2 and local code requirements to identify design airflow rates within dwelling units For commercial applications, follow local code requirements and/or ASHRAE 62.1 requirements |
Ensure system ability to maintain the desired humidity |
- SF
- MF
Specification | Objective |
---|---|
Locate equipment in an area with access to HVAC supply trunk line or plenum, and orient outside air intake so the effective length of the duct run is as short as possible |
Easy access to existing ductwork and fresh air source |
- SF
- MF
Specification | Objective |
---|---|
Mount ventilator using mechanical fasteners per manufacturer's specifications and applicable code (e.g., seismic restraints) Isolate unit from the building framing unless specifically designed to be directly attached |
Secure, vibration-isolated dehumidifier |
- SF
- MF
Specification | Objective |
---|---|
Install ventilator according to manufacturer specifications and applicable code |
Correct installation |
- SF
- MF
Specification | Objective |
---|---|
Install all electrical wiring according to manufacturer specifications and applicable code |
Prevent an electrical hazard |
- SF
- MF
Specification | Objective |
---|---|
Install dehumidistat in accordance with manufacturer specifications Operation of the dehumidifier will be based upon humidity/temperature in the return air, or will provide supply air at a specified temperature and humidity |
Controls support dehumidification strategy |
- SF
- MF
Specification | Objective |
---|---|
Seal all air moving portions of the system using UL 181 products without interfering with the function of dampers |
Airtight ventilation system with freely operating dampers |
- SF
- MF
Specification | Objective |
---|---|
Connect condensate drain according to manufacturer specifications to a drain location approved by applicable code Insulate all condensate lines outside the thermal boundary to a minimum of R-4 |
Safe and reliable condensate drainage |
- SF
- MF
Specification | Objective |
---|---|
Ensure fan, service disconnect switch, filters, and drains are accessible for maintenance according to NEC, or applicable building code |
Serviceable parts are readily accessible |
- SF
- MF
Specification | Objective |
---|---|
If fire dampers are required in the fresh air supply duct, install them according to applicable building code Fire dampers must be accessible for inspection and/or testing Sealing activities must not interfere with the operation of fire dampers, balancing dampers, or backdraft dampers |
Fire dampers function effectively and are accessible |