Version 2020 | 08/14/2020 - 14:23 | 4.0104.6e | Installation | Apply SPF to prescribed R-value in a continuous layer over entire surface of knee wall from roof deck to attic floor air barrier using a pass thickness maximum in accordance with manufacturer specifications In colder climates (IECC Zones 5-8), install SPF to a thickness of at least a class II vapor retarder or have at least a class II vapor retarder coating or covering in direct contact with the underside of the SPF |
Continuous and contiguous pressure and thermal boundary that prevents vapor intrusion |
Black Line | ||
Version 2020 | 08/14/2020 - 14:23 | 4.0104.6e | Installation | Apply SPF to prescribed R-value in a continuous layer over entire surface of knee wall from roof deck to attic floor air barrier using a pass thickness maximum in accordance with manufacturer specifications In colder climates (IECC Zones 5-8), install SPF to a thickness of at least a class II vapor retarder or have at least a class II vapor retarder coating or covering in direct contact with the underside of the SPF |
Continuous and contiguous pressure and thermal boundary that prevents vapor intrusion |