Version 2020 | 08/14/2020 - 14:25 | 4.0401.3f | Ignition and thermal barriers | If foam is no more than 3 1/4" thick and the space is not permanently habitable no thermal barrier is required If foam is thicker than 3 1/4", doesn't meet the flame and smoke index, or is of less than 0.5 lb/ft3 density, or the space is permanently habitable, separate foam from the subspace with a suitable thermal barrier covering or coating as indicated in manufacturer's specifications and applicable building code If code requirements are unclear, consult local code officials for clarification |
Minimize ignition and combustion potential |
Black Line | ||
Version 2020 | 08/14/2020 - 14:25 | 4.0401.3f | Ignition and thermal barriers | If foam is no more than 3 1/4" thick and the space is not permanently habitable no thermal barrier is required If foam is thicker than 3 1/4", doesn't meet the flame and smoke index, or is of less than 0.5 lb/ft3 density, or the space is permanently habitable, separate foam from the subspace with a suitable thermal barrier covering or coating as indicated in manufacturer's specifications and applicable building code If code requirements are unclear, consult local code officials for clarification |