| SWS Version | Created | Specification ID | Title | Specification | Objective | Rationale | Status |
|---|---|---|---|---|---|---|---|
| Version 2020 | 08/14/2020 - 14:25 | 5.0102.1c | Slope | Install condensate piping with not less than 1/8" per foot (1% slope) towards the termination point |
Condensate drains toward termination |