Specification History
SWS Version | Created | Specification ID | Title | Specification | Objective | Supporting Materials | Rationale | Status |
---|---|---|---|---|---|---|---|---|
Version 2020 | 08/14/2020 - 14:25 | 5.0104.1a | Material selection | Select insulation: with a flame spread and smoke development index of 25/50 when tested in accordance with ASTM E84 or UL 723 and that includes an exterior vapor retarder layer Select duct materials: with a flame spread of no more than 25 when tested in accordance with ASTM E84 or UL 723 and that are UL 181, SMACNA, NAIMA approved or conform to ASTM A653 |
Select durable and safe materials |
Black Line | ||
Version 2020 | 08/14/2020 - 14:25 | 5.0104.1a | Material selection | Select insulation: with a flame spread and smoke development index of 25/50 when tested in accordance with ASTM E84 or UL 723 and that includes an exterior vapor retarder layer Select duct materials: with a flame spread of no more than 25 when tested in accordance with ASTM E84 or UL 723 and that are UL 181, SMACNA, NAIMA approved or conform to ASTM A653 |
Select durable and safe materials |
Black Line |