Version 2020 | 08/14/2020 - 14:26 | 5.0108.4l | Condensate drainage | Install a secondary drain pan with a float switch interlocked to the system power under all condensing units that exist in or above conditioned space Pipe condensate to a properly sized sanitary drain or the outdoors and provide with traps as specified by the manufacturer and applicable building code When there is potential for condensation or freezing of the drain line, insulate condensate drain lines to a minimum of R-4 with insulation that contains a Class II or greater vapor retarder |
Prevent water damage and drain condensate through functional drains to an approved location |
Black Line | ||
Version 2020 | 08/14/2020 - 14:26 | 5.0108.4l | Condensate drainage | Install a secondary drain pan with a float switch interlocked to the system power under all condensing units that exist in or above conditioned space Pipe condensate to a properly sized sanitary drain or the outdoors and provide with traps as specified by the manufacturer and applicable building code When there is potential for condensation or freezing of the drain line, insulate condensate drain lines to a minimum of R-4 with insulation that contains a Class II or greater vapor retarder |