Specification History
SWS Version | Created | Specification ID | Title | Specification | Objective | Supporting Materials | Rationale | Status |
---|---|---|---|---|---|---|---|---|
Version 2020 | 08/14/2020 - 14:26 | 6.0101.1a | Material selection | Select duct materials that have a flame spread no greater than 25 Select flexible ducts that are UL 181 listed or Air Diffusion Council approved Select rigid ducts of 28 gauge or thicker Select duct insulation with a flame spread/smoke development index of 25/50 or less when tested according to ASTM E84 or UL 723 |
Select durable, safe, and effective duct materials |
Black Line | ||
Version 2020 | 08/14/2020 - 14:26 | 6.0101.1a | Material selection | Select duct materials that have a flame spread no greater than 25 Select flexible ducts that are UL 181 listed or Air Diffusion Council approved Select rigid ducts of 28 gauge or thicker Select duct insulation with a flame spread/smoke development index of 25/50 or less when tested according to ASTM E84 or UL 723 |
Select durable, safe, and effective duct materials |
Black Line |