Version 2020 08/14/2020 - 14:27 6.0301.2b Intake location

Install intake to pull air from the outdoors, which does not include unconditioned spaces such as attics and crawl spaces that are ventilated with the outdoors

Install intake:

A minimum of 6" from grade;

A minimum of 10' from contaminant sources or exhaust outlets;

Above local snow or flood line;

A minimum of 18" above an asphalt based roof;

Never on a flat roof

Unrestricted entry of contaminant-free air