Version 2020 08/14/2020 - 14:27 6.0302.1c Termination location

Terminate exhaust system to the outdoors, which does not include unconditioned spaces such as attics and crawl spaces that are ventilated with the outdoors

Install terminations: A minimum of 3' away from any property line; A minimum of 3' away from operable opening to houses; A minimum of 10' away from mechanical intake; Above the snow-line

If the termination is at the soffit, seal soffit vents within 6' of the termination

Prevent exhaust from reentering the structure