Specification History
SWS Version | Created | Specification ID | Title | Specification | Objective | Supporting Materials | Rationale | Status |
---|---|---|---|---|---|---|---|---|
Version 2020 | 08/14/2020 - 14:27 | 6.0303.1c | Exterior exhaust termination location | Terminate exhaust system to the outdoors, which does not include unconditioned spaces such as attics and crawl spaces that are ventilated with the outdoors Install terminations: A minimum of 3' away from any property line; A minimum of 3' away from operable opening to houses; A minimum of 10' away from mechanical intake; Above the snow-line If the termination is at the soffit, seal soffit vents within 6' of the termination |
Prevent exhaust from reentering the structure |
Black Line | ||
Version 2020 | 08/14/2020 - 14:27 | 6.0303.1c | Exterior exhaust termination location | Terminate exhaust system to the outdoors, which does not include unconditioned spaces such as attics and crawl spaces that are ventilated with the outdoors Install terminations: A minimum of 3' away from any property line; A minimum of 3' away from operable opening to houses; A minimum of 10' away from mechanical intake; Above the snow-line If the termination is at the soffit, seal soffit vents within 6' of the termination |
Prevent exhaust from reentering the structure |
Black Line |