Specification History
SWS Version | Created | Specification ID | Title | Specification | Objective | Supporting Materials | Rationale | Status |
---|---|---|---|---|---|---|---|---|
Version 2020 | 08/14/2020 - 14:27 | 7.0103.4a | Selection | Select exit signs: from the NEMA Premium Exit Sign List and that meet all applicable codes (UL 924, NFPA 70, and/or IBC and IFC, as appropriate) that include battery-backups that can maintain the total load for a minimum period of 1-1/2 hours and indicate system failure with visual and audible alarm that are able to be attached to the existing outlet box that are rated for a maximum of 5 watts per illuminated side with at least a 1-year warranty |
Select efficient, reliable, and safe lighting improvements |
Black Line | ||
Version 2020 | 08/14/2020 - 14:27 | 7.0103.4a | Selection | Select exit signs: from the NEMA Premium Exit Sign List and that meet all applicable codes (UL 924, NFPA 70, and/or IBC and IFC, as appropriate) that include battery-backups that can maintain the total load for a minimum period of 1-1/2 hours and indicate system failure with visual and audible alarm that are able to be attached to the existing outlet box that are rated for a maximum of 5 watts per illuminated side with at least a 1-year warranty |
Select efficient, reliable, and safe lighting improvements |
Black Line |