Continuous, weathertight air and thermal boundary
Specifications
- SF
- MH
- MF
Specification | Objective |
---|---|
Select sealants that: are compatible with their intended surfaces, allow for differential expansion and contraction between dissimilar materials, meet the requirements of the applicable fire safety code (e.g., thermal or ignition barriers), and for use inside the pressure boundary select low volatile organic compound (VOC) sealants that meet independent testing and verification protocols |
Select safe and effective sealants |
- SF
- MH
- MF
Specification | Objective |
---|---|
Select: pest-resistant materials that adequately support applied load and are permanent air barriers, materials that meet the requirements of the applicable fire safety code (e.g., thermal or ignition barriers), and low volatile organic compound (VOC) materials for use inside the pressure boundary that meet independent testing and verification protocols |
Select safe and effective materials |
- SF
- MH
- MF
Specification | Objective |
---|---|
Select windows that meet the SHGC, U-value, and air leakage requirements of the work order Select windows that meet the egress and safety glass requirements of the location where they are installed |
Choose correct and safe new window |
- SF
- MH
- MF
Specification | Objective |
---|---|
Remove existing window stops, sashes, parting strips, pulleys, and weights Insulate and seal existing window weight pockets if they will remain after new installation Replace any damaged or rotting framing Remove any material from the sealing area that will prevent full adhesion of the selected sealant Remove any material from the installation area that will prevent a level and firm installation Seal the rough opening to the wall system's air and thermal boundary with non-expanding sealants Install flashing to direct water away from the window opening in accordance with manufacturer's instructions |
Rough opening sealed, insulated, and properly prepared for installation |
- SF
- MH
- MF
Specification | Objective |
---|---|
Install new window in accordance with manufacturer specifications in alignment with the wall system's air and thermal boundary Install flashing per the manufacturer's specifications Gaps between the new window and existing opening will be sealed with low-expanding foam or equivalent sealant Final installation will be air and watertight |
Continuous and contiguous air and thermal boundary |
- SF
- MH
- MF
Specification | Objective |
---|---|
Verify safe operation and size of egress windows as required by local codes |
Safe egress maintained |