Continuous, contiguous, safe, and compliant thermal boundary that prevents air movement @ 50 Pascals
Specifications
- SF
- MH
- MF
Specification | Objective |
---|---|
Verify that installation area is free of: active water leaks, fuel leaks (i.e., gas, oil, propane), and pest intrusions energized knob and tube wiring uncovered electrical junctions improperly terminated devices (ventilation fans, dryers, plumbing stacks, condensate lines, combustion appliance flues/chimneys, supply and/or return air ducts, etc.) unshielded high-temperature devices (non-IC rated recessed lights, chimneys, flues, vents, etc.) unless they are zero clearance devices insulation escape openings Verify that installation area is: intact and able to support insulation weight |
Ensure space can be safely insulated |
- SF
- MH
- MF
Specification | Objective |
---|---|
Remove existing insulation and vapor retarders from installation area Cover all finished surfaces areas (e.g., windows, doors) in the installation area with appropriate materials (e.g., plastic, masking tape) Install durable backing material over any escape holes in the air barrier and ensure utility junctions remain accessible per local code requirements |
Protect finished surfaces from overspray and prevent SPF leakage |
- SF
- MH
- MF
Specification | Objective |
---|---|
Apply SPF to prescribed R-value in a continuous layer over entire surface of wall from bottom plate to top plate using a pass thickness maximum in accordance with manufacturer specifications |
Continuous pressure and thermal boundary |
- SF
- MH
- MF
Specification | Objective |
---|---|
Separate all foam products from living space with a thermal barrier material (e.g., 1/2" gypsum wallboard) as specified by applicable building code If attic is used only for the service of utilities, foam will be separated from the attic space using a suitable ignition barrier covering or coating according to manufacturer's specifications If attic is used for storage or occupancy, spray foam will be separated from the attic space using a thermal barrier material (e.g., 1/2" gypsum wallboard) as specified by applicable building code and manufacturer specifications If code requirements are unclear, consult local code officials for clarification |
Minimize ignition and combustion potential |
- SF
- MH
- MF
Specification | Objective |
---|---|
Post a dated receipt signed by the installer that minimally includes: Installed insulation type, coverage area, installed thickness, minimum settled thickness, installed R-value, and number of bags installed |
Comply with 16 CFR 460.17 and document contract compliance |