SPF Insulation

Detail ID 4.0201.1
Topic
Walls
Subtopic
Accessible Walls
Desired Outcome

Continuous, contiguous, safe, and compliant thermal boundary that prevents air movement @ 50 Pascals

SF Single Family Site-Built Housing
MH Manufactured Housing
MF Multifamily Housing

Specifications

  • SF
  • MH
  • MF
Specification Objective

Verify that installation area is free of:

active water leaks, fuel leaks (i.e., gas, oil, propane), and pest intrusions

energized knob and tube wiring

uncovered electrical junctions

improperly terminated devices (ventilation fans, dryers, plumbing stacks, condensate lines, combustion appliance flues/chimneys, supply and/or return air ducts, etc.)

unshielded high-temperature devices (non-IC rated recessed lights, chimneys, flues, vents, etc.) unless they are zero clearance devices

insulation escape openings

Verify that installation area is:

intact and able to support insulation weight

Ensure space can be safely insulated

  • SF
  • MH
  • MF
Specification Objective

Select insulation that has a flame spread and smoke development index of 75/450 or less when tested in accordance with ASTM E84 or UL 723

Select fire safe materials

  • SF
  • MH
  • MF
Specification Objective

Remove existing insulation and vapor retarders from installation area

Cover all finished surfaces areas (e.g., windows, doors) in the installation area with appropriate materials (e.g., plastic, masking tape)

Install durable backing material over any escape holes in the air barrier and ensure utility junctions remain accessible per local code requirements

Protect finished surfaces from overspray and prevent SPF leakage

  • SF
  • MH
  • MF
Specification Objective

Remove contaminants from all SPF application surfaces that will prevent full adhesion or cause degradation

Verify all SPF application surfaces are in accordance with manufacturer specifications for moisture content and temperature

Properly bonded SPF installation

  • SF
  • MH
  • MF
Specification Objective

Apply SPF to prescribed R-value in a continuous layer over entire surface of wall from bottom plate to top plate using a pass thickness maximum in accordance with manufacturer specifications

Continuous pressure and thermal boundary

  • SF
  • MH
  • MF
Specification Objective

Separate all foam products from living space with a thermal barrier material (e.g., 1/2" gypsum wallboard) as specified by applicable building code

If attic is used only for the service of utilities, foam will be separated from the attic space using a suitable ignition barrier covering or coating according to manufacturer's specifications

If attic is used for storage or occupancy, spray foam will be separated from the attic space using a thermal barrier material (e.g., 1/2" gypsum wallboard) as specified by applicable building code and manufacturer specifications

If code requirements are unclear, consult local code officials for clarification

Minimize ignition and combustion potential

  • SF
  • MH
  • MF
Specification Objective

Post a dated receipt signed by the installer that minimally includes: Installed insulation type, coverage area, installed thickness, minimum settled thickness, installed R-value, and number of bags installed

Comply with 16 CFR 460.17 and document contract compliance

View Sub-Topic:
Accessible Walls
Next Detail:
Batt Insulation