Continuous, contiguous, safe, and compliant thermal boundary
Specifications
- SF
- MH
- MF
Specification | Objective |
---|---|
Verify that installation area is free of: active water leaks, fuel leaks (i.e., gas, oil, propane), and pest intrusions energized knob and tube wiring improperly terminated devices (ventilation fans, dryers, plumbing stacks, condensate lines, combustion appliance flues/chimneys, etc.) unshielded high-temperature devices (non-IC rated recessed lights, chimneys, flues, vents, etc.) unless they are zero clearance devices insulation escape openings Verify that installation area is: intact, able to support insulation weight, and air sealed |
Ensure space can be safely insulated |
- SF
- MH
- MF
Specification | Objective |
---|---|
Select sealants that: are compatible with their intended surfaces allow for differential expansion and contraction between dissimilar materials meet the requirements of the applicable fire safety code (e.g., thermal or ignition barriers) |
Select safe and effective sealants |
- SF
- MH
- MF
Specification | Objective |
---|---|
Remove all exterior cladding from the installation area Seal all holes, gaps, and penetrations in existing sheathing airtight Remove any existing insulation or protrusions that prevent full insulation contact with existing air barrier Replace any rotten or structurally weak substrate |
Provide secure attachment for insulation in full contact with the exterior sheathing |
- SF
- MH
- MF
Specification | Objective |
---|---|
Insulation will either be installed fully in contact with the exterior sheathing, or a drainage plane will be installed that allows moisture to drain completely to outdoors from behind the rigid insulation |
Prevent moisture buildup behind insulation layer |
- SF
- MH
- MF
Specification | Objective |
---|---|
Install continuous rigid insulation to prescribed R-value using mechanical fasteners that penetrate sub-framing a minimum of 1-1/2" Overlap seam of multiple layers a minimum of 12" Seal all insulation seams, joints and connections in each layer with compatible sealant (caulk, tape, mastic, etc.) |
Continuous pressure and thermal boundary of correct R-value |
- SF
- MH
- MF
Specification | Objective |
---|---|
Reinstall exterior cladding using mechanical fasteners over the new insulation per the manufacturer's specifications |
Weathertight cladding installation |
- SF
- MH
- MF
Specification | Objective |
---|---|
Ensure that insulation retrofit complies with applicable code regarding fire separation |
- SF
- MH
- MF
Specification | Objective |
---|---|
Post a dated receipt signed by the installer that minimally includes: Installed insulation type, coverage area, installed thickness, and installed R-value |
Comply with 16 CFR 460.17 and document contract compliance |