Continuous, contiguous, and safe thermal boundary
Specifications
- MH
Specification | Objective |
---|---|
Verify that installation area is free of: active water leaks, fuel leaks (i.e., gas, oil, propane), and pest intrusions improperly terminated devices (ventilation fans, dryers, plumbing stacks, condensate lines, combustion appliance flues/chimneys, etc.) unshielded high-temperature devices (non-IC rated recessed lights, chimneys, flues, vents, etc.) unless they are zero clearance devices Verify that installation area is: intact, able to support insulation weight and pressure, and air sealed |
Ensure space can be safely insulated |
- MH
Specification | Objective |
---|---|
Remove objects from the interior surfaces of the walls being insulated Repair or reattach interior paneling as necessary |
Protect occupant belongings and prevent interior paneling failure |
- MH
Specification | Objective |
---|---|
Remove skirting if it overlaps the siding Remove fasteners from the bottom of the siding, working upward until the siding can be pulled away from the framing approximately 6" without damaging the siding Install temporary fasteners at the seams near the bottom of the siding panels to prevent separation Cut access through sheathing if present |
Access cavities without damaging the siding or compromising the interior wall surface |
- MH
Specification | Objective |
---|---|
Install insulation in entirety of each cavity to a density of no more than 1.6 pounds per cubic foot between the interior paneling and any existing insulation Do not overfill any portion of the cavity |
Consistent thermal boundary that does not compromise interior wall |
- MH
Specification | Objective |
---|---|
Patch or repair sub sheathing as necessary If skirting was removed, reinstall it to shed water to the outside of the skirting Reattach siding with new fasteners and without bulges or wrinkles |
Weathertight exterior cavity closure |
- MH
Specification | Objective |
---|---|
Post a dated receipt signed by the installer that minimally includes: Installed insulation type, coverage area, installed thickness, minimum settled thickness, installed R-value, and number of bags installed |
Comply with 16 CFR 460.17 and document contract compliance |