Continuous, contiguous, safe, pest and weather resistant thermal boundary that prevents air movement @ 50 Pascals
Specifications
- SF
- MF
Specification | Objective |
---|---|
Verify that installation area is free of: active water leaks, fuel leaks (i.e., gas, oil, propane), and pest intrusions energized knob and tube wiring uncovered electrical junctions improperly terminated devices (ventilation fans, dryers, plumbing stacks, condensate lines, combustion appliance flues/chimneys, etc.) unshielded high-temperature devices (non-IC rated recessed lights, chimneys, flues, vents, etc.) unless they are zero clearance devices insulation escape openings Verify that installation area is: intact, able to support insulation weight, and air sealed |
Ensure space can be safely insulated |
- SF
- MF
Specification | Objective |
---|---|
Select insulation that has a flame spread and smoke development index of 75/450 or less and backing material that has a smoke development index of 450 or less when tested in accordance with ASTM E84 or UL 723 Select rigid backing material that: is a permanent air barrier will support installed insulation without failure |
Select fire safe materials |
- SF
- MF
Specification | Objective |
---|---|
Select sealants that: are compatible with their intended surfaces allow for differential expansion and contraction between dissimilar materials meet the requirements of the applicable fire safety code (e.g., thermal or ignition barriers) |
Select safe and effective sealants |
- SF
- MF
Specification | Objective |
---|---|
Remove existing insulation and vapor retarders from installation area Install durable backing material over any escape holes in the air barrier Install flags that can be seen below the floor joists at all utility junctions for future identification and ensure utility junctions remain accessible per local code requirements |
Prevent condensation and SPF leakage |
- SF
- MF
Specification | Objective |
---|---|
Apply SPF to prescribed R-value to bottom side of floor deck and top of support beams using a pass thickness maximum as indicated by manufacturer specifications Install to a thickness of a class I vapor retarder or have a class I vapor retarder coating or covering in direct contact with the underside of the SPF |
Continuous pressure and thermal boundary that prevents moisture vapor movement |
- SF
- MF
Specification | Objective |
---|---|
Mechanically fasten a continuous rigid barrier to underside of floor assembly that is suitable to withstand weather, moisture, and pest contact, and with a fire-resistance rating equal to the resistance rating of the original floor assembly |
Insulation protected from weather, pests, and moisture |
- SF
- MF
Specification | Objective |
---|---|
Seal all seams, joints, connections, penetrations, etc. in the rigid protective barrier with compatible sealant Stuff any gaps larger than 1/4" with copper metal mesh or steel wool prior to sealing Cover exposed corners of the rigid protective barrier with reinforced hardware cloth or metal board bead |
Airtight, pest resistant exterior |
- SF
- MF
Specification | Objective |
---|---|
Apply a weather-resistant barrier to the exposed side of the insulation (e.g., exterior insulated finishing system and spray-on roof waterproofing over foam) |
Protect insulation from weather, light and impact |
- SF
- MF
Specification | Objective |
---|---|
Separate all foam products from living space with a thermal barrier material (e.g., 1/2" gypsum wallboard) as specified by applicable building code If code requirements are unclear, consult local code officials for clarification |
Minimize ignition and combustion potential |
- SF
- MF
Specification | Objective |
---|---|
Post a dated receipt signed by the installer that minimally includes: Installed insulation type, coverage area, installed thickness, and installed R-value |
Comply with 16 CFR 460.17 and document contract compliance |