Continuous, contiguous, moisture resistant, and safe thermal boundary that prevents air movement @ 50 Pascals
Specifications
- SF
- MF
Specification | Objective |
---|---|
Verify that installation area is free of: active water leaks, fuel leaks (i.e., gas, oil, propane), and pest intrusions energized or undammed knob and tube wiring uncovered electrical junctions improperly terminated devices (ventilation fans, dryers, plumbing stacks, condensate lines, combustion appliance flues/chimneys, etc.) unshielded high-temperature devices (non-IC rated recessed lights, chimneys, flues, vents, etc.) unless they are zero clearance devices insulation escape openings Verify that installation area: is intact, able to support insulation weight, and air sealed has a sealed class I vapor retarder installed over all bare earth has all bulk sources of moisture directed away from the subspace walls (i.e., gutters, flashing, grading, drainage) |
Ensure space can be safely insulated |
- SF
- MF
Specification | Objective |
---|---|
Select sealants that: are compatible with their intended surfaces allow for differential expansion and contraction between dissimilar materials meet the requirements of the applicable fire safety code (e.g., thermal or ignition barriers) are low volatile organic compound (VOC) sealants for use inside the pressure boundary that meet independent testing and verification protocols |
Select safe and effective sealants |
- SF
- MF
Specification | Objective |
---|---|
Remove any incomplete or unsealed vapor barrier from the foundation wall |
Prevent condensation |
- SF
- MF
Specification | Objective |
---|---|
Install insulation to prescribed R-value in full contact with the entire perimeter of foundation wall from ceiling to floor If insulation has a vapor retarder on only one side install it facing the conditioned space Install insulation to prescribed R-value in full contact with the If insulation has a vapor retarder on only one side install it facing the conditioned space |
Contiguous and continuous thermal barrier Contiguous and continuous thermal barrier |
- SF
- MF
Specification | Objective |
---|---|
Attach rigid or batt insulation with mechanical fasteners |
Insulation remains in place |
- SF
- MF
Specification | Objective |
---|---|
Seal all seams, joints, connections, etc. of insulation on the conditioned side of the assembly, or install a sealed air barrier on the conditioned side of the insulation (e.g., drywall, luan) |
Continuous air barrier on heated side of assembly |
- SF
- MF
Specification | Objective |
---|---|
If termite pressure exists, maintain a 3" inspection gap from the top of the insulation to the bottom of any wood |
Allow for termite detection |
- SF
- MF
Specification | Objective |
---|---|
Separate all foam products from living space with a thermal barrier material (e.g., 1/2" gypsum wallboard) as specified by applicable building code If space is used only for the service of utilities, foam will be separated from the space using a suitable ignition barrier covering or coating according to manufacturer's specifications If space is used for storage or occupancy, foam will be separated from the space using a thermal barrier material (e.g., 1/2" gypsum wallboard) as specified by applicable building code and manufacturer specifications If code requirements are unclear, consult local code officials for clarification |
Minimize ignition and combustion potential |
- SF
- MF
Specification | Objective |
---|---|
Post a dated receipt signed by the installer that minimally includes: Installed insulation type, coverage area, installed thickness, and installed R-value |
Comply with 16 CFR 460.17 and document contract compliance |