Continuous, contiguous, moisture resistant, and safe thermal boundary that prevents air movement @ 50 Pascals
Specifications
- SF
- MF
Specification | Objective |
---|---|
Verify that installation area is free of: active water leaks, fuel leaks (i.e., gas, oil, propane), and pest intrusions energized or undammed knob and tube wiring uncovered electrical junctions improperly terminated devices (ventilation fans, dryers, plumbing stacks, condensate lines, combustion appliance flues/chimneys, etc.) unshielded high-temperature devices (non-IC rated recessed lights, chimneys, flues, vents, etc.) unless they are zero clearance devices insulation escape openings Verify that installation area: is intact, able to support insulation weight, and air sealed has a sealed class I vapor retarder installed over all bare earth has all bulk sources of moisture directed away from the subspace walls (i.e., gutters, flashing, grading, drainage) |
Ensure space can be safely insulated |
- SF
- MF
Specification | Objective |
---|---|
Install a continuous drainage plane at the interior surface of the exterior basement wall or leave an airspace of at least 1/2" between insulated wall assembly and foundation wall from the top of the wall to a drainage field at the bottom of the wall or sub-slab that drains to outdoors If foundation is rough (i.e., rubble, stone), install a waterproof membrane to which insulation will adhere |
Remove bulk moisture from interior surface of basement wall |
- SF
- MF
Specification | Objective |
---|---|
Install insulation to prescribed R-value in a continuous boundary around the entire perimeter of foundation wall from top of band joist to floor, in contact with any waterproof membrane that exists at the foundation wall Install insulation to prescribed R-value in a continuous boundary around the |
Contiguous and continuous thermal barrier Contiguous and continuous thermal barrier |
- SF
- MF
Specification | Objective |
---|---|
If termite pressure exists, maintain a 3" inspection gap from the top of the insulation to the bottom of any wood and if subslab drainage is installed, termite treatment will be performed |
Allow for termite detection |
- SF
- MF
Specification | Objective |
---|---|
Attach rigid or batt insulation with mechanical fasteners or other means that has a minimum service life of 20 years |
Insulation remains in place |
- SF
- MF
Specification | Objective |
---|---|
Install a continuous air barrier between the foundation and the interior of the basement that spans from the slab to the subfloor above Seal all seams, joints, connections, etc. of insulation on the conditioned side or create an airtight wall assembly on the conditioned side of the insulation |
Continuous air barrier on heated side of assembly |
- SF
- MF
Specification | Objective |
---|---|
Separate all foam products from living space with a thermal barrier material (e.g., 1/2" gypsum wallboard) as specified by applicable building code If space is used only for the service of utilities, foam will be separated from the space using a suitable ignition barrier covering or coating according to manufacturer's specifications If space is used for storage or occupancy, spray foam will be separated from the space using a thermal barrier material (e.g., 1/2" gypsum wallboard) as specified by applicable building code and manufacturer specifications If code requirements are unclear, consult local code officials for clarification |
Minimize ignition and combustion potential |
- SF
- MF
Specification | Objective |
---|---|
Do not install a vapor retarder layer on either side of the wall (e.g., vinyl wallpaper, polyethylene, latex paint) |
Allow wall to dry to the interior |
- SF
- MF
Specification | Objective |
---|---|
Post a dated receipt signed by the installer that minimally includes: Installed insulation type, coverage area, installed thickness, and installed R-value |
Comply with 16 CFR 460.17 and document contract compliance |