Leak free, safe, efficient, effective, and compliant refrigerant line installation
Specifications
- SF
- MH
- MF
Specification | Objective |
---|---|
Size refrigerant lines in accordance with manufacturer specifications for the installed equipment |
Piping moves appropriate volume of refrigerant without increasing compressor load |
- SF
- MH
- MF
Specification | Objective |
---|---|
Install refrigerant lines without kinks, crimps, or excessive bends Route lines in a manner that protects it from damage by workers and occupants Join lines using manufacturer-approved method(s) Install proper filter dryer(s) on all systems Install P-traps on suction line risers that are greater than 10' in height Use manufacturer specifications to determine appropriate lengths and elevations of refrigerant lines between condensing units and indoor coils |
Durable, safe piping that moves appropriate volume of refrigerant and protects compressor functionality |
- SF
- MH
- MF
Specification | Objective |
---|---|
Insulate all suction lines to a minimum of R-4 with an insulation that is a class II or better vapor retarder Insulate all high pressure lines that pass through spaces where condensation may occur to a minimum of R-4 with an insulation that is a class II or better vapor retarder Seal all seams, joints, etc. of insulation using compatible material (e.g., tape) Install UV-resistant insulation on exterior lines or protected insulation from UV degradation |
Prevent excessive heat gain, condensation and UV degradation |
- SF
- MH
- MF
Specification | Objective |
---|---|
Secure and support refrigerant lines according to applicable code and in a manner that protects the line from damage by workers or occupants |
Prevent excessive line movement |
- SF
- MH
- MF
Specification | Objective |
---|---|
If refrigerant lines are installed where they may be contacted by vehicles, people, tree limbs, etc., install a rigid sleeve or pipe duct over them that provides adequate impact protection |
Lines protected from impact damage |
- SF
- MH
- MF
Specification | Objective |
---|---|
Install locking refrigerant caps on all refrigerant access ports |
Protect occupants and the environment from unintentional refrigerant discharge or theft |