Ducts securely fastened
Specifications
- SF
- MH
- MF
Specification | Objective |
---|---|
Fasten ducts with a minimum of three equally spaced galvanized or stainless steel mechanical fasteners |
Durable joints |
- SF
- MH
- MF
Specification | Objective |
---|---|
Fasten ducts with UL 181 approved tie bands using a tie band tensioning tool |
Durable and sealed joints |
- SF
- MH
- MF
Specification | Objective |
---|---|
Install a rigid metal coupling of the same size as the flex duct between the two sections Fasten both joints with UL 181 approved tie bands using a tie band tensioning tool |
Durable flex duct connections |
- SF
- MH
- MF
Specification | Objective |
---|---|
Cut duct board edges to create an overlapping joint on all contact surfaces Fasten joints with outward clinching (stitch) staples spaced every 2" Cover joint with UL 181 rated mastic embedded fiber tape and additional mastic that laps at least 1" past the edges of the tape on all sides |
Durable and sealed joints |
- SF
- MH
- MF
Specification | Objective |
---|---|
Install a metal take-off collar on the duct board specifically designed for the thickness of the duct board Bend all finger tabs down securely so collar shank is firmly seated against the exterior surface Attach flexible duct to collar with UL 181 approved tie bands using a tie band tensioning tool |
Durable take-off duct attachment |
- SF
- MH
- MF
Specification | Objective |
---|---|
Fasten duct board to metal duct using metal channel and mechanical fasteners spaced evenly on all sides Cover connection joint with UL 181 rated mastic embedded fiber tape and additional mastic that laps at least 1" past the edges of the tape on all sides |
Durable and sealed duct connection |
- SF
- MH
- MF
Specification | Objective |
---|---|
Fasten duct board to air handler cabinet using metal channel fastened with screws spaced a maximum of 6" with the duct board sandwiched between the channel flanges In upflow air handler connections, install a flexible connection between supply plenum and unit that does not reduce the inside dimensions of the duct |
Durable connection that reduce duct vibration and optimize airflow |
- SF
- MH
- MF
Specification | Objective |
---|---|
Fasten boot to wood using a minimum of 1 stainless steel or galvanized fastener per side |
Durable boot to subfloor connection |
- SF
- MH
- MF
Specification | Objective |
---|---|
If accessible, fasten a boot hanger to adjacent framing with mechanical fasteners Connect boot to hanger with mechanical fasteners If inaccessible, fasten boot to gypsum with UL 181 rated fiber tape and mastic |
Durable boot to gypsum connection |
- SF
- MH
- MF
Specification | Objective |
---|---|
Install a flexible connection between plenum and unit that does not reduce the inside dimensions of the duct Fasten plenum on all sides with mechanical fasteners spaces no more than every 6" |
Durable joints that reduce duct vibration and optimize airflow |