Duct Support

Detail ID 5.0105.2
Topic
Forced Air
Subtopic
Duct Repair
Desired Outcome

Ducts properly and durably supported

SF Single Family Site-Built Housing
MH Manufactured Housing
MF Multifamily Housing

Specifications

  • SF
  • MH
  • MF
Specification Objective

Support flexible and duct board ducts and plenums with 1-1/2" wide or greater material, installed every 4' or less, without crimping or pinching the ductwork or reducing the interior dimensions

Ducts must never contact the ground

Ducts securely supported without causing interior dimensions to be reduced or allowing moisture damage

  • SF
  • MH
  • MF
Specification Objective

Support metal ducts with 1/2" wide or greater eighteen gauge metal straps, 12-gauge galvanized wire, or metal rods every 10' or less

Ducts must never contact the ground

Ducts securely supported and protected from corrosion

  • SF
  • MH
  • MF
Specification Objective

Support upflow supply plenums or downflow return plenums independently from the air handler attachment

Prevent plenum sagging or excessive movement