Safe and durable SPF duct insulation
Specifications
- SF
- MH
- MF
Specification | Objective |
---|---|
Remove contaminants from all SPF application surfaces that will prevent full adhesion or cause degradation Verify all SPF application surfaces are in accordance with manufacturer specifications for moisture content and temperature Cover all holes, cracks, gaps, etc. where SPF may enter the interior of the duct with a temporary backing material (e.g., foil tape) |
Properly bonded SPF only on the exterior of ducts |
- SF
- MH
- MF
Specification | Objective |
---|---|
Airtight and properly insulated ducts that do not threaten indoor air quality |
- SF
- MH
- MF
Specification | Objective |
---|---|
Separate all foam products from living space with a thermal barrier material (e.g., 1/2" gypsum wallboard) as specified by applicable building code If space is used only for the service of utilities, foam will be separated from the space using a suitable ignition barrier covering or coating according to manufacturer's specifications If space is used for storage or occupancy, spray foam will be separated from the space using a thermal barrier material (e.g., 1/2" gypsum wallboard) as specified by applicable building code and manufacturer specifications If code requirements are unclear, consult local code officials for clarification |
Minimize ignition and combustion potential |
- SF
- MH
- MF
Specification | Objective |
---|---|
Post a dated receipt signed by the installer that minimally includes: Installed insulation type, coverage area, installed thickness, and installed R-value |
Comply with 16 CFR 460.17 and document contract compliance |