Safe, compliant, efficient, and effective system installation in which sequence of operation is correct
Specifications
- SF
- MH
- MF
Specification | Objective |
---|---|
Perform residential load calculation in accordance with the current version of ANSI/ACCA Manual J (Residential Load Calculation) or equivalent using interior design temperatures of 75 degrees for cooling and 70 degrees for heating Perform commercial load calculation in accordance with the current version of ANSI/ACCA Manual N (Commercial Load Calculation) or equivalent using interior design temperatures of 75 degrees for cooling and 70 degrees for heating Room by room load calculations will be performed when installing a new duct system or in retro-commissioning projects Calculated loads based on post-retrofit dwelling characteristics |
Equipment design load calculated correctly for post-retrofit dwelling |
- SF
- MH
- MF
Specification | Objective |
---|---|
Select residential equipment in accordance with the current version of ANSI/ACCA Manual S (Residential Equipment Selection) or equivalent Select commercial equipment in accordance with the current version of ANSI/ACCA Manual CS (Commercial Applications, Systems and Equipment) or equivalent Select cooling equipment capable of meeting the sensible and latent load of the building that is not sized more than 115% of total load or next available size Select heating equipment of the lowest capacity required to meet the design heating load and provide the air volume required by any air conditioning equipment installed Select system that is ENERGY STAR® certified or equivalent Select outdoor units that are corrosion-protected for marine climate zones |
Select efficient equipment capable of meeting the design loads |
- SF
- MH
- MF
Specification | Objective |
---|---|
Locate unit to provide clearance on all sides and top according to manufacturer specifications and service access according to applicable code |
Locate outdoor unit to facilitate air-flow and service access |
- SF
- MH
- MF
Specification | Objective |
---|---|
Situate outdoor unit on a non-wicking equipment pad Ensure unit is level, stable, and elevated a minimum of 6" above the ground |
Stable outdoor unit that is protected from corrosion |
- SF
- MH
- MF
Specification | Objective |
---|---|
Locate unit in a dry location and within conditioned space (when feasible) that provides adequate service access according to manufacturer specifications and applicable code |
Protect unit from corrosion and thermal loss and facilitate service access |
- SF
- MH
- MF
Specification | Objective |
---|---|
Safe, accessible, stable, and properly installed indoor unit with safe and durable fuel supply |
- SF
- MH
- MF
Specification | Objective |
---|---|
Ensure unit is level, stable, secured to ductwork, properly braced to prevent movement (seismic bracing), and elevated as required by applicable building code |
Safe, stable, and durably supported indoor unit |
- SF
- MH
- MF
Specification | Objective |
---|---|
Support equipment on a fireproof platform that is elevated above the insulation level or suspend with threaded rod in accordance with local codes and manufacturer specifications Install vibration pads/isolators according to manufacturer specifications |
Equipment is safe, stable, level, and does not transmit vibration or reduce attic insulation level |
- SF
- MH
- MF
Specification | Objective |
---|---|
Support equipment on a nonwicking, fireproof material or suspend with threaded rod in accordance with local codes and manufacturer specifications Install vibration pads/isolators according to manufacturer specifications |
Equipment is safe, stable, level, and does not transmit vibration or corrode |
- SF
- MH
- MF
Specification | Objective |
---|---|
Support equipment on a durable, fireproof platform capable of supporting the weight of the equipment Install vibration pads/isolators according to manufacturer specifications |
Equipment is safe, stable, level, and does not transmit vibration or corrode |
- SF
- MH
- MF
Specification | Objective |
---|---|
Support equipment on ductwork capable of supporting the weight of the equipment |
Equipment is safe, stable, and level |
- SF
- MH
- MF
Specification | Objective |
---|---|
Install equipment connections (e.g., electrical service, condensate drains, ductwork, fuel, venting, refrigerant lines) to allow for necessary service and repair access to all portions of the equipment |
Connections do not interfere with operation and service of equipment |
- SF
- MH
- MF
Specification | Objective |
---|---|
Locate all intakes/terminations in compliance with manufacturer specifications and applicable building code |
System intakes/terminations that are operational, safe, and compliant |
- SF
- MH
- MF
Specification | Objective |
---|---|
Install a secondary drain pan with a float switch interlocked to the cooling system power under all units that exist in or above conditioned space Pipe condensate to a properly sized sanitary drain or the outdoors and provide with traps as specified by the manufacturer and applicable building code When there is potential for condensation or freezing of the drain line, insulate condensate drain lines to a minimum of R-4 with insulation that contains a Class II or greater vapor retarder |
Prevent water damage and drain condensate through functional drains to an approved location |
- SF
- MH
- MF
Specification | Objective |
---|---|
Install electrical wiring according to NFPA 70, and Provide an electrical disconnect within site of the unit Install all high voltage wiring inside of protective conduit and approved junction boxes, no wiring connections (high or low voltage) will occur outside of appropriate junction box |
Safe and compliant electrical wiring installation |
- SF
- MH
- MF
Specification | Objective |
---|---|
Install refrigerant piping according to SWS detail "Refrigerant Lines" Install refrigerant charge according to SWS detail "Refrigerant Charge" |
Safe, and effective refrigerant installation |
- SF
- MH
- MF
Specification | Objective |
---|---|
Install smoke detectors inside the supply duct plenum of systems that move more than 2,500 cubic feet per minute (CFM) in accordance with the applicable building code |
Operational fire warning system in place |
- SF
- MH
- MF
Specification | Objective |
---|---|
Seal air handler and adjoining ductwork in accordance with SWS Subtopic "Duct Sealing" If air handler is installed in a building cavity (i.e., closet), seal the cavity to eliminate any return air leaks from adjoining chases |
Air handler leakage less than 1% of system airflow |
- SF
- MH
- MF
Specification | Objective |
---|---|
Provide occupants/owners with user's manual, warranty information, installation instructions, and installer contact information |
Provide occupants and service technicians with instructions |