Safe, compliant, efficient, and effective system installation in which sequence of operation is correct
Specifications
- SF
- MH
- MF
Specification | Objective |
---|---|
Perform residential load calculation in accordance with the current version of ANSI/ACCA Manual J (Residential Load Calculation) or equivalent using interior design temperatures of 75 degrees for cooling and 70 degrees for heating Perform commercial load calculation in accordance with the current version of ANSI/ACCA Manual N (Commercial Load Calculation) or equivalent using interior design temperatures of 75 degrees for cooling and 70 degrees for heating Room by room load calculations will be performed when installing a new duct system or in retro-commissioning projects Calculated loads based on post-retrofit dwelling characteristics |
Equipment design load calculated correctly for post-retrofit dwelling |
- SF
- MH
- MF
Specification | Objective |
---|---|
Select residential equipment in accordance with the current version of ANSI/ACCA Manual S (Residential Equipment Selection) or equivalent Select commercial equipment in accordance with the current version of ANSI/ACCA Manual CS (Commercial Applications, Systems and Equipment) or equivalent Select cooling equipment capable of meeting the sensible and latent load of the building that is not sized more than 115% of total load or next available size Select heating equipment of the lowest capacity required to meet the design heating load and provide the air movement required by any air conditioning equipment installed Select system that is ENERGY STAR® certified or equivalent Select outdoor units that are corrosion-protected for marine climate zones |
Select equipment capable of meeting the design loads |
- SF
- MH
- MF
Specification | Objective |
---|---|
Locate unit to provide clearance on all sides and top according to manufacturer specifications and service access according to applicable code |
Locate outdoor unit to facilitate air-flow and service access |
- SF
- MH
- MF
Specification | Objective |
---|---|
Situate outdoor unit on a non-wicking equipment pad Ensure unit is level, stable, and secured to ductwork |
Stable unit that is protected from corrosion |
- SF
- MH
- MF
Specification | Objective |
---|---|
Safe and compliant installation with safe and durable fuel supply |
- SF
- MH
- MF
Specification | Objective |
---|---|
Install electrical wiring according to NFPA 70, and Provide an electrical disconnect within site of the unit Install all high voltage wiring inside of protective conduit and approved junction boxes, no wiring connections (high or low voltage) will occur outside of appropriate junction box |
Safe and compliant electrical wiring installation |
- SF
- MH
- MF
Specification | Objective |
---|---|
Install refrigerant piping according to SWS detail "Refrigerant Lines" Install refrigerant charge according to SWS detail "Refrigerant Charge" |
Safe, and effective refrigerant installation |
- SF
- MH
- MF
Specification | Objective |
---|---|
Install equipment connections (e.g., electrical service, condensate drains, ductwork, fuel, venting, refrigerant lines) to allow for necessary service and repair access to all portions of the equipment |
Connections do not interfere with operation and service of equipment |
- SF
- MH
- MF
Specification | Objective |
---|---|
Install exterior ductwork using rigid, corrosion-resistant metal insulated to a minimum of R-12 |
Durable, pest-resistant, and insulated exterior ductwork |
- SF
- MH
- MF
Specification | Objective |
---|---|
Locate all intakes/terminations in compliance with manufacturer specifications and applicable building code |
System intakes/terminations that are operational, safe, and compliant |
- SF
- MH
- MF
Specification | Objective |
---|---|
Pipe condensate to a safe outdoor location where it is drained without contacting the outdoor unit and provide the condensate piping with traps as specified by the manufacturer and applicable building code When there is potential for freezing of the drain line, insulate condensate drain lines to a minimum of R-4 with insulation that contains a Class II or greater vapor retarder |
Drain condensate away from unit and prevent damage |
- SF
- MH
- MF
Specification | Objective |
---|---|
Install smoke detectors inside the supply duct plenum of systems that move more than 2,500 cubic feet per minute (CFM) in accordance with the applicable building code |
Operational fire warning system in place |
- SF
- MH
- MF
Specification | Objective |
---|---|
Provide occupants/owners with user's manual, warranty information, installation instructions, and installer contact information |
Provide occupants and service technicians with instructions |