Safe, compliant, efficient, and effective system installation in which sequence of operation is correct
Specifications
- SF
- MH
- MF
Specification | Objective |
---|---|
Perform residential load calculation in accordance with the current version of ANSI/ACCA Manual J (Residential Load Calculation) or equivalent using interior design temperatures of 75 degrees for cooling and 70 degrees for heating Perform commercial load calculation in accordance with the current version of ANSI/ACCA Manual N (Commercial Load Calculation) or equivalent using interior design temperatures of 75 degrees for cooling and 70 degrees for heating Room by room load calculations will be performed when installing multiple indoor units Calculated loads based on post-retrofit dwelling characteristics |
Equipment design load calculated correctly for post-retrofit dwelling |
- SF
- MH
- MF
Specification | Objective |
---|---|
Select residential equipment in accordance with the current version of ANSI/ACCA Manual S (Residential Equipment Selection) or equivalent Select commercial equipment in accordance with the current version of ANSI/ACCA Manual CS (Commercial Applications, Systems and Equipment) or equivalent Select system that is ENERGY STAR® certified or equivalent Select outdoor units that are corrosion-protected for marine climate zones When applicable, supply multiple indoor units with a single outdoor unit using manufacturer specifications to determine allowable overage of indoor unit capacity in relation to the outdoor unit and derated capacity of indoor units based on outdoor design temperature When applicable, select units that offer ducting options (e.g., ceiling cassette units have a knock out for a 5" or 6" duct) and/or have an outdoor air intake |
Select equipment capable of meeting the design loads Equipment operates at optimal efficiency and reduced cost |
- SF
- MH
- MF
Specification | Objective |
---|---|
Locate unit with manufacturer recommended clearance on all sides and to allow service access according to applicable code |
Outdoor unit located to facilitate air-flow and service access |
- SF
- MH
- MF
Specification | Objective |
---|---|
Situate outdoor unit on a non-wicking equipment pad Ensure unit is level, plumb, stable, and elevated a minimum of 6" above snow line |
Stable outdoor unit that is protected from corrosion |
- SF
- MH
- MF
Specification | Objective |
---|---|
Locate indoor unit(s) to provide effective airflow to desired locations without exceeding the manufacturer specifications for refrigerant line total length Maintain clearances in accordance with manufacturer specifications |
Effective location selected for indoor unit(s) |
- SF
- MH
- MF
Specification | Objective |
---|---|
Insulate concealed ceiling cassette unit(s) to a minimum of R-6 when contained inside a building cavity, (even when inside the thermal boundary) without hindering access to serviceable parts Insulation must include a sealed vapor retarder layer |
Prevent water damage to structure |
- SF
- MH
- MF
Specification | Objective |
---|---|
Securely mount indoor unit(s) according to manufacturer specifications ensuring condensate drainage is correctly sloped |
Securely mounted with properly functioning drain pan |
- SF
- MH
- MF
Specification | Objective |
---|---|
Install electrical wiring according to NFPA 70, and Provide an electrical disconnect within site of the outdoor unit Install all high voltage wiring inside of protective conduit and approved junction boxes, no wiring connections (high or low voltage) will occur outside of appropriate junction box |
Safe and compliant electrical wiring installation |
- SF
- MH
- MF
Specification | Objective |
---|---|
Locate all intakes/terminations in compliance with manufacturer specifications and applicable building code |
System intakes/terminations that are operational, safe, and compliant |
- SF
- MH
- MF
Specification | Objective |
---|---|
Install equipment connections (e.g., electrical service, condensate drains, ductwork, refrigerant lines) to allow for necessary service and repair access to all portions of the equipment |
Equipment connections do not interfere with operation and service of equipment |
- SF
- MH
- MF
Specification | Objective |
---|---|
When applicable, install ducting per the manufacturer specifications in runs that do not exceed 6' per run Insulate all ducts, including those inside the thermal boundary, to a minimum of R-6 with insulation that includes a sealed vapor barrier |
Low static pressure ducts that are condensation-resistant |
- SF
- MH
- MF
Specification | Objective |
---|---|
Total equivalent length of refrigerant piping will not exceed system manufacturer specifications Install refrigerant piping according to SWS detail "Refrigerant Piping" Install refrigerant charge according to SWS detail "Refrigerant Charge" |
Safe and effective refrigerant piping |
- SF
- MH
- MF
Specification | Objective |
---|---|
Install wall mounted thermostats that are not within the direct airflow of the indoor unit |
Independent system controls that are not affected by supply air |
- SF
- MH
- MF
Specification | Objective |
---|---|
Install an independent condensate drain for each indoor unit according to SWS for "Condensate Disposal" Install a float switch in the drain pan that interlocks with the cooling system power to turn unit off when pan is not draining Pipe condensate to a properly sized sanitary drain or the outdoors When there is potential for condensation or freezing of the drain line, insulate condensate drain lines to a minimum of R-4 with insulation that contains a Class II or greater vapor retarder |
Independent and functional condensate drainage that prevents water damage |
- SF
- MH
- MF
Specification | Objective |
---|---|
Provide occupants/owners with user's manual, warranty information, installation instructions, and installer contact information |
Provide occupants and service technicians with instructions |