Safe, compliant, efficient, and effective system installation in which sequence of operation is correct
Specifications
- SF
- MH
- MF
Specification | Objective |
---|---|
Select installation location based on service and utility access, occupant safety, and area to be cooled |
Safe, accessible, and effective location |
- SF
- MH
- MF
Specification | Objective |
---|---|
Safe, secure, and accessible installation |
- SF
- MH
- MF
Specification | Objective |
---|---|
Install unit a minimum of 3" above the ground on a solid durable pad (e.g., concrete slab) or Suspended a minimum of 6" above the ground using secure and durable supports Secure unit per applicable seismic restraint needs Ensure unit is level, stable, and mechanically secured to any ductwork |
Safely supported and level installation |
- SF
- MH
- MF
Specification | Objective |
---|---|
Install equipment connections (e.g., electrical service, condensate drains, ductwork, fuel, venting, refrigerant lines) to allow for necessary service and repair access to all portions of the equipment |
Connections do not interfere with operation and service of equipment |
- SF
- MH
- MF
Specification | Objective |
---|---|
Install electrical wiring according to NFPA 70, and Provide an electrical disconnect within site of the unit Install all high voltage wiring inside of protective conduit and approved junction boxes, no wiring connections (high or low voltage) will occur outside of appropriate junction box |
Safe and compliant electrical wiring installation |
- SF
- MH
- MF
Specification | Objective |
---|---|
Install a float switch in the pan that is interlocked to the system power to prevent unit from overflowing Pipe overflow tube to a properly sized sanitary drain or the outdoors and provided with traps as specified by the manufacturer and applicable building code Install a back-flow preventor on the potable water supply |
Prevent water damage, and potable water contamination |
- SF
- MH
- MF
Specification | Objective |
---|---|
Locate intakes no closer than 10' to pollutant sources or a minimum of 3' below the source |
Protect occupant health |
- SF
- MH
- MF
Specification | Objective |
---|---|
Provide occupants/owners with user's manual, warranty information, installation instructions, and installer contact information |
Provide occupants and service technicians with instructions |