Combustion furnaces serviced as needed
Specifications
- SF
- MH
- MF
Specification | Objective |
---|---|
Verify proper function and safety of the following system elements: Thermostat, ignition system, gas valves, venting system, safety devices, blower motor, electrical wiring, gas piping, condensate disposal |
Ensure all components function properly, safely, efficiently, and are durable |
- SF
- MH
- MF
Specification | Objective |
---|---|
Perform combustion testing that includes the following: Carbon monoxide, combustion efficiency, gas pressure testing, temperature rise, stack temperature Adjust combustion as needed to meet BPI 1200 standards for carbon monoxide Clean the following elements: Furnace cabinet interior, blower fan and motor, heat exchangers, burners Lubricate all moving parts according to manufacturer specifications Replace return air and fresh air supply filters Remove combustible/flammable materials from furnace area Repair or replace additional elements as needed |
Replace/clean necessary parts |
- SF
- MH
- MF
Specification | Objective |
---|---|
Post on equipment, or in a conspicuous location, a list of all systems and components inspected, results, and services performed that includes legible service personnel name, contact information, and date of service |
Verify contract completion |