PTAC/PTHP Units

Detail ID 5.0301.2
Topic
Non-Distributed
Subtopic
Room Conditioning
Desired Outcome

Efficient, safe, and compliant dwelling conditioning that functions as designed

SF Single Family Site-Built Housing
MH Manufactured Housing
MF Multifamily Housing

Specifications

  • SF
  • MF
Specification Objective

Perform residential load calculation in accordance with the current version of ANSI/ACCA Manual J (Residential Load Calculation) or equivalent using interior design temperatures of 75 degrees for cooling and 70 degrees for heating

Calculated loads based on post-retrofit dwelling characteristics

Equipment design load calculated correctly for post-retrofit dwelling

  • SF
  • MF
Specification Objective

Select new unit that:

is ENERGY STAR® qualified or equivalent

does not use electric resistance heat as the primary heat source (i.e., select Heat Pump units)

is corrosion-resistant in marine climates

is ducted if conditioning multiple rooms

Select efficient, corrosion-resistant system that conditions intended area

  • SF
  • MF
Specification Objective

Install unit per manufacturer specifications and in accord with applicable building code

Where applicable, unit controls and thermostat must comply with the operable parts provisions of ICC A117.1 when the dwelling unit is required to be accessible per ADA

Where required, maintain egress requirements in accordance with ANSI/NFPA 101 and local laws

Safe, compliant, and accessible installation that meets egress requirements

  • SF
  • MF
Specification Objective

Pipe condensate away from the building or to a sanitary drain

Insulate condensate drain to a minimum of R-3 if danger of freezing or condensation exists

Functional condensate drain

  • SF
  • MF
Specification Objective

Before installing through-wall unit, seal all adjacent framing and provide a sealed and sleeved opening

After installation, seal the perimeter with suitable materials (e.g., ASTM C1193)

Reduce air movement around installed unit

  • SF
  • MF
Specification Objective

If unit is ducted, insulate all cooling ducts (including those inside the thermal boundary) in accordance with SWS Detail "General Duct Insulation"

Prevent water damage from condensation

  • SF
  • MF
Specification Objective

Permanently remove equipment from job site and recycle or dispose of removed equipment and refrigerant in accordance with local and federal law (e.g., EPA Section 608 of Clean Air Act of 1990)

Permanently decommission old equipment

Old equipment is permanently removed from service, protect the environment, and comply with regulation

  • SF
  • MF
Specification Objective

Provide occupants/owners with user's manual, warranty information, installation instructions and installer contact information

Provide occupants and service technicians with instructions